Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T04FR00111
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2004 | VIOL - FIRE PROTECTION SYSTEMS | Approved | TFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Shall have the hood system cleaned from roof top to kitchen area. When finished no grease shall be on roof. |
|
05/10/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11.6.3 Hood Cleaning. Shall clean filters to hood system, need to set up maintenance program to keep filters clean. |
|
05/10/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Shall have a up to date inspection done on hood extingushing system and a copy of the report sent to Fire Prevention at 797 E. Ajo. |
|
05/10/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Shall have all fire extingushers inspected, this shall be done on a yearly bases. |