COMPLAINT:MIN HOUSING- LIVE UNCOVERED WIRES HANGING FROM CEILING IN THE BEDROOM.

Outstanding Inspections

Case Number: T04DV00691
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 16
End Date Description Inspector Results Comments
NPO - UNSECURED BUILD OR STRUC None Not Inspected
VIOL(BL) - LIVING AREAS None Not Inspected
VIOL(BL) - ROOF None Not Inspected
NPO(EL)-MAIN/PANEL/SUB/DISCONT None Not Inspected
VIOL(EL) - CIRCUITS None Not Inspected
VIOL(EL)-SUBPANELS/DISCONNECTS None Not Inspected
NPO(EL)-WIRING/SWITCH/OUTLT/FX None Not Inspected
VIOL(EL) - FIXTURES None Not Inspected
NPO(PL)-GAS SUPPLY/CONNECT None Not Inspected
NPO(PL)-WATER HEATERS None Not Inspected
NPO(HC)-NO VENTILATION None Not Inspected
NPO(HC)-HEATING & VENTILATION None Not Inspected
VIOL(SA) - BATHS None Not Inspected
VIOL(SA) - KITCHEN None Not Inspected
VIOL(FS) - HAZARDOUS STORAGE None Not Inspected
NPO - SMOKE ALARMS None Not Inspected

Completed Inspections

Case Status: COMPLIAN
Case Number: T04DV00691
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date Description Inspector Results Comments
09/22/2004 INSP - INITIAL CODE ENFORCMENT HLOPEZ Approved VISITED SITE ON INITIAL INSP OF UNIT 2926. PRESENT WERE OWNER ED & PARTNER JEAN CREAGAN. DID INSPECTION OF EFFICIENCY UNIT . ELECTRICAL: (1) ALL RECEPTACLES WERE CHECKED GFIC IN BATHROOM IS GOOD, GFIC IN KITCHEN SHOWS HOT, NEUTRAL ARE REVERSED. (2) SOME 3 PRONG RECEPTACLES SHOW NO GROUND. (3) 3 RECEPTACLES IN KITCHEN ARE WITH IN 6 FEET OF WATER & WILL REQUIRE GFIC PROTECTION. (4) BASE BOARD HEATER IS NOT HARDWIRED TO ELECTRICAL SERVICE (PERMIT REQUIRED) WEATHER PROOFING. (5) ENTRY DOOR LACKING TRESHOLD & WEATHER STRIPPING. MECH: WALL FURNACE NOT WORKING HAS BEEN CAPPED OFF, D.S.D. WILL REQUIRE REMOVAL OF WALL FURNACE, STRUCTURE IS LACKING GAS SERVICE, HOT WATER IS PROVIDED BY MAIN HOT WATER TANK AT 2924 ADDRESS. TENANT HAS MICROWAVE FOR COOKING, GAS STOVE IS NOT HOOKED UP. PICTURES WERE TAKEN.
11/09/2004 INSP - FOLLOW UP CODE ENFORCE HLOPEZ Approved VISITED SITE, MET WITH OWENRS ED AND JEAN, ALSO PRESENT WERE INSP. M LOPEZ FROM E.S AND TFD INSP. W. CUMMING WENT OVER NOV ISSUED ON 09/30/04. VIOLATION ABATED ARE AS FOLLOWS: ADDRESS 2924 1. ABATED - SMOKE DETECTOR HAVE BEEN INSTALLED. 2. 1. NOT ABATED WILL CONTACT ELECTRICAL CONTRACTOR FOR INFORMATION. 2. ABATED - 3 PRONG RECEPTACLES HAVE BEEN INSTALLED. 3. ABATED - COVER PLATE REINSTALLED ON JUNCTION BOX, ALL COVER PLATES HAVE BEEN REINSTALLED. 4. ABATED - EXPOSED ELECTRICAL CONDUCTORS WERE REMOVED AND LIGHT FIXTURE RECEPTACLE HAS BEEN DISABLED. 5. ABATED - ARMORED FLEX WAS INSTALLED FOR EXPOSED ELECTRICAL CONDUCTOR. 6. ABATED - BROKEN REEPTACLE HAS BEEN REPLACED. 3. 1 - ITEMS 1, 2, 3 & 4 HAVE NOT BEEN ABATED. CONTRACTOR WORKING ON ABATING ISSUES. PERMIT HAS BEEN ISSUED T04CM04902. 5 - ABATED - REGISTER HAS BEEN INSTALLED. 6 - ABATED - EXHAUST FAN HAS BEEN INSTALLED AND IS COVERED UNDER PERMIT ISSUED (SEE ITEM 5). 4. NOT ABATED, WORK IN PROGRESS. 5. NOT ABATED - LACKING WEATHER STRIPPING - THRESHOLD INSTALLED. 6. 1 & 2 ABATED - VEGETATION WAS TRIMMED, TRASH AND DEBRIS REMOVED. 7. NOT ABATED - CAR AND TRUCK TO BE REMOVED BY THIS WEEKEND 11/12/04. ADDRESS 2926 8. 1- ABATED - REVERSED HOT AND NEUTRAL CORRECTED. 2- ABATED - 3 PRONG RECEPTACLES WERE REMOVED. 3- GFIC OUTLETS WERE INSTALLED. ABATED. 4- ABATED - BASE BOARD HEATER WAS INSTALLED UNDER PERMIT. 9. NOT ABATED - LACKING WEATHER STRIPPING, THRESHOLD WAS INSTALLED. 10. ABATED - ILLEGAL WALL FURNACE WAS REMOVED. 11. NOT ABATED. 12. ABATED, VEGETATION TRIMMED AND REMOVED. ADDRESS 2928 A 13. 1 & 2 ABATED - PROTECTIVE GRILL INSTALLED AS WELL AS EXHAUST VENT. 14. ABATED, MECHANICAL GROUNDS REPAIRED. 15. ABATED - EXTERIOR WATER LINE WERE COVERED WITH 1" FOAM INSULATION. 16. ABATED - CEILING WAS REPAIRED. 17. 1- ABATED EXTERIOR HOLES WERE COVERED AND SEALED. 2- NOT ABATED. 18. NOT ABATED - COMPOST PILE HAS NOT BEEN ADDRESS NOR HAS DOWNED TREE REMOVED. TENANT WANTS TO KEEP FOR FIREWOOD. 19. ABATED - CAR WAS REMOVED. ADDRESS 2928 B 20. ABATED DOOR CAUSING COMPLETED AND NEW THRESHOLD INSTALLED. 21. ABATED - ALL BROKEN WINDOWS REPLACED AND SEALED. 22. NOT ABATED - PEST CONTROL SCHEDULED FOR 11/12/04. 23. 1. ABATED - EXPOSED ELECTRICAL CONDUCTORS WERE REMOVED 2. ABATED -EXPOSED ELECTRICAL CONDUCTOR WERE SECURED AND INSTALLED IN J-BOX. 3. NOT ABATED - CONTACT ELECTRICAL CONTRACTOR FOR INFORMATION. 4. ABATED - HAZARDOUS PANEL REMOVED UNDER PERMIT. 24. 1 - NOT ABATED NO PERMIT WAS ISSUED FOR UNIT B, DNR TO CHECK RECORDS PERMIT WAS ISSUED FOR UNIT 2928A 2. ABATED, I INCH FOAM INSULATION WAS INSTALLED. 25. ABATED - TRASH AND DEBIRS WERE REMOVED. 26. NOT ABATED. WORKING ON REMOVING DIRT CONTAMINATED BY OIL. ADDRESS 2930A 27. ABATED 1 & 2 TRASH AND DEBRIS REMOVED, VEGETATION TRIMMED. 28. ABATED - WINDOW REPAIRED TO ALLOW FOR PROPER EGRESS 29. ABATED- WINDOW REPAIRED AND WILL OPEN TO ALLOW FOR VENTILATION 30. ABATED - GFIC OUTLET REMOVED, WIRES CAPPED, BLANK PLATE INSTALLED. 31. 1- ABATED - EXHAUST VENT OPENING CLEARED 2- ABATED - FLEX LINE AND GAS VALVE RELOCATED. 32. 1- ABATED - COOLER SUPPLY LINE REPAIRED. 2- ABATED - 1 IN CLEARANCE HAS BEEN PROVIDED AT ENCLOSURE LID. 3- ABATED - BATHROOM SINK RESEARCH TO WALL AND SEALED. 4- ABATED - TOILET RESECURED TO CLOSET FLANGE AND CAULKED AROUND TOILET. 33. 1-ABATED - CRACKS WERE SEALED AND PAINTED, WALL BY TUB REPAIRED. 2. ABATED - NEW DOOR WITH JAMB INSTALLED. 34. 1- ABATED - DOUBLE KEYED LOCK REMOVED AND REPLACED WITH DEAD BOLT WITH THUMB THROW. 2- ABATED - BEDROOM PRIVACY LOCK REPLACED. 35. ABATED - WEATHER STRIPPING INSTALLED. 36. NOT ABATED - WORK IS ON GOING. 37. ABATED - NEW NUMBER INSTALLED MEET TFD REQUIREMENTS. 38. ABATED - DOULBE KEYED DEAD BOLT REPLACE W/THUMB THOW TYPE. 39. ABATED - WINDOW OPENS TO ALLOW FOR SAFE EGREES. 40. ABATED - VEGETATION TRIMMED AND REMOVED. 41. 1- ABATED - SMOKE DETECTOR INSTALLED. 2- ABATED - WINDOW REPAIRED TO ALLOW FOR SAFE EGRESS. 42. 1- ABATED - B & M HEATING CONTRACTOR SERVICED WALL HEATER. 2 - ABATED - COVER HAS BEEN SECURED. 43. ABATED - RECEPTACLE WAS REMOVED, CONDUCTORS CAPPED OFF, BLANK PLATE INSTALLED. 44. ABATED - EXHAUST FAN REPAIRED. 45. 1 - ABATED - LEAKING P-TRAP REPAIRED. 2- NOT ABATED - ANGLE STOP VALVE FOUND TO BE LEAKING 3- ABATED -HOSE BIB HANDLE INSTALLED. 46. ABATED - DOUBLE KEYED DEAD BOLT ASSEMBLY REMOVED AND REPLACED WITH THROW TYPE. 47. 1 - ABATED - BROKEN WINDOW REPLACED. 2 - DOOR REPLACED AND MOLDING REPAIRED ABATED 3 - ABATED - WINDOW PANE SEALED. 4 - NOT ABATED - WORK IN PROGRESS 5 - ABATED - CRACKS WERE SEALED. 48. ABATED - ALL COMBUSTIBLES WERE REMOVED. 49. ABATED - AS PER TFD REQUIREMENTS. 50. ABATED - SMOKE DETECTOR INSTALLED. 51. ABATED - DOULBE KEYED DEAD BOLT ASSEMBLY REPLACE WITH THUMB THOW TYPE. 52. ABATED, WINDOW REPAIRED TO ALLOW FOR PROPER EGRESS. 53. ABATED - VEGETATION WAS WAS TRIMMED AND REMOVED. 54. NOT ABATED - NO DECISION HAS BEEN MADE ON KEEPING UNIT AS HABITABLE SPACE. OWNER GETTING BIDS. 55. ABATED VEGETATION WAS REMOVED AND TRIMMED. (PARKING LOT) OWNER HAS MADE EXCELLENT PROGRESS WILL EXTEND ABATEMENT PRIOR TO 45 DAYS FOR REMAINING VIOLATIONS. OWNER HAS PROVIDED COPIES OF ALL ELECTRICAL REPAIRS DONE BY BENGAL ELECTRIC AND COPIES OF POSTED INSPECTION REQUEST.

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T04DV00691
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
Date Name
09/01/2004 COURT ORDERED ABATEMENT
04/12/2005 VIOLATION CLOSED
09/01/2004 CONTACTED OWNER BY PHONE
09/08/2004 OWNER CONTACTED INSP. BY PHONE
12/29/2004 UPDATE: