Case Details

Status:

Closed - Resolved

Type:

RMIN: Unit # 103A: No A/C per tenant
Address:

Entered Date:

06/18/2025

Applicant:

N/A

Description:

Completed Inspections

Case Status: Closed - Resolved
Case Number: CE-VIO0625-02654
Case Description: RMIN: Unit # 103A: No A/C per tenant
Total Completed Inspections - 2
End Date Description Inspector Results Comments
06/18/2025 COT - ENFC - Code Enforcement - Initial In Violation 405 pm - Contact w/ tenants on site. Thermostat is set to Cool on Auto, system produces cool air, but not cold air. Thermostat says interior temp is 88. Temperature probe in kitchen shows 90. Two outlets in kitchen have no power. A breaker is off, however tenant is unsure as to why. There are missing breakers/openings into breaker panel. Called and spoke with property manager. -VM
07/10/2025 COT - ENFC - Code Enforcement - Follow Up Passed 1126 AM - Followup at unit. Breaker slots have been installed in the breaker panel. All violations have been abated, close case. -VM