Description:

Completed Inspections

Case Status: Closed - Resolved
Case Number: CE-VIO0625-02502
Case Description: RMIN / Home/Office / No air (cooler) needs water pump
Total Completed Inspections - 2
End Date Description Inspector Results Comments
06/18/2025 COT - ENFC - Code Enforcement - Initial In Violation 313 pm - Contact w/ resident on site. When swamp cooler is turned on, it generates hot air. Took temperature w/ temperature probe. Reading is at 90.0 degrees in kitchen, 90.5 in southwest bedroom. Two south bedrooms lack smoke detectors. North west bedroom smoke detector cannot be tested. Hallway is lacking a smoke detector. Issued NOV to property manager on site. -VM
07/01/2025 COT - ENFC - Code Enforcement - Follow Up In Violation 157 PM - Contact with tenant on site. Swamp cooler has been repaired, it is producing cool air, however the air is not cool enough to cool the unit to the temperature as required by code. I took temperatures with a temperature probe inside the unit. Temperature in living room is at 87 degrees, and temperature in kitchen is at 87.2 degrees. Additional work may be required to bring evaporative cooler into better working order. Will be looking to move to a citation. -VM