Permit Number: T22CM07565
Parcel: 12107462D

Address:
5902 E PIMA ST

Review Status: Active

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM07565
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2022 ANY FIRE REVIEW Active
10/03/2022 ANY WATER REVIEW Active
10/04/2022 SHASEMA1 ENGINEERING REVIEW Passed
10/12/2022 WBERGER1 ZONING REVIEW Approved
10/12/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
10/18/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07565

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. No construction type has been provided. Provide the correct construction type.
2. The waiting room has not been included in the occupant load calculation as it is an assembly space. Provide corrected occupant load calculations.
3. Corridors are required to be rated in accordance with Table 1020.1. Provide correctly rated corridors.
4. Doors in the rated corridor wall are required to be rated as well. Provide correctly rated corridor walls in accordance with Section 716.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov