Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
10/13/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. The International Plumbing Code, 2018, and the International Fuel Gas Code, 2018is the controlling code for this structure, not the International Residential Code. Reference: Section 101.2, IPC 2018.
3. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
4. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1 , 504, 606.1, and 607.3, IPC 2018.
5. Section 604.1, IPC 2018 allows water distribution systems to be designed using accepted engineering methods. Provide the source of the method used to determine the water demand and size the water distribution system for each dwelling unit.
6. For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2018.
10/18/2022 JGARCIA1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. The International Building Code, 2018 is the controlling code for this structure, not the International Residential Code.
3. Provide a narative detailing overall scope of work.
4. Identify locations of all structural damage and proposed repairs.
5. General: Please provide written responses to all review comments.
10/18/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Reference: Electrical plans.

1 Provide Electrical power and lighting plans sealed and design by an Arizona Registrant.

2 This is a commercial project. Revise references to the IRC with the currently adopted 2017 NEC.

3 Provide complete compliance with the 2012 Outdoor Lighting Code (OLC) for exterior lighting. Be advised per 2012 (OLC), modifications to any exterior lighting on the Parcel will require the entire Parcel to be brought up to current OLC compliance as applicable. See section 102.4 (OLC)

4 The last Electrical Note on plan sheet #9 is incorrect. All 120volt branch circuits shall be protected by a combination Arc Fault device or OCPD. See NEC 210.12(A).

Ref; 2018 IBC sec 107.1,107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 City of Tucson/Pima County Outdoor Lighting Code, (OLC).

Final Status

Task End Date Reviewer's Name Type of Review Description
10/18/2022 VVERA1 OUT TO CUSTOMER Completed