Permit Number: T22CM07036
Parcel: 11708223A

Address:
902 S 6TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM07036
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/23/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM07036
902 S 6ht Ave – C-3
TI Add Additional Bedrooms– (1st Review)

TRANSMITTAL: September 23, 2022

This site is located in C-3 Zone (UDC Article 4.7.22), multi-family use is permitted in the zone, (UDC Table 4.8-4).

1. As you are adding additional bedrooms and this will affect vehicle parking a Development package will be required. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/23/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed
09/23/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/03/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/03/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/03/2022 JPEELDA1 FIRE REVIEW Approved
10/03/2022 ROBERT SHERRY WATER REVIEW Completed
10/05/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.
1. Provide tamper resistant receptacles.
2. Show the location of the breaker panel and verify that wall modifications does not locate it in a bathroom or closet.
2017 NEC art 406.12, 240.24.(D)(E).