| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Provide a detailed description as to the scope of work required to install New and or Replacement luminaires, including wiring methods, branch circuit and Breaker panel designations, Panel load calculations and lighting controls, where applicable. 1 Ref; Site Plan and Lumen calculations. The type ‘D’ luminaires are not accounted for in the calculations. Also provide shielding type information (Manufacture Cut Sheet) for the replacement ‘D’ String Lighting as indicated in the Light Fixture Schedule. If the replacements are now indicated as type ‘E’ fixtures, show them as such on the Light Fixture Schedule and the Site Lighting Plan.. The note for Special inspection is incorrect. 104.2.1 is not the correct section requiring a special inspection. See section 106.2.1. The value is 100,000, not 1000,000 lumens per acre. Based on this section 106.2.1, a special inspection is required. Show the location(s) of the Type ‘A’ wall sconce (Check typo in the light fixture schedule “Sconce”). Identify the existing type ‘F’ pole lighting on the site plan. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/05/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |