Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM06956
Parcel: 133231470

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM06956
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/12/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Please contact Pima County Addressing to have suite added into the system Phone #:520-724-9512 Email: addressing@pima.gov
09/15/2022 IMONSHI1 ZONING REVIEW Approved
09/15/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
09/26/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM06956


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Denied
1. Provide an updated occupant load calculation. The spaces have been reconfigured to where the occupant loads will need to be calculated. Provide an updated occupant load calculation in accordance with Section 1004.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E2.1A ELECTRICAL POWER RENOVATION PLAN - AREA A: Two sets of office furniture share the same sets of circuits in lower left of sheet. Correct if required.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
First Plumbing Review:
-Each Coffee maker water connection on M3.1C Needs its own ASSE 1024 Backflow

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/03/2022 JVINCEN1 FIRE REVIEW Approved
10/11/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2022 VVERA1 OUT TO CUSTOMER Completed