Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/10/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 Verify what device or equipment will be utilized to initiate the Rapid Shutdown function and apply the ‘Rapid Shutdown’ label to this device or equipment. NEC 690.56 2 Verify the location of the Rapid Shutdown device or equipment complies with NEC 690.12(C). 3 Provide a grounding detail on the plans for the New Electrical Service per NEC 250 and the module racking system. Also verify NEC 690, Part 5. 4 Provide evidence on the electrical plans that the Rapid Shutdown function meets the requirements of NEC art 690.12(B)(1)(2)(3)(4), boundaries around modules and maximum voltage requirements. 5 Verify Ground Fault and Arc Fault protection is provided NEC 690.41(B), 690.11. 6 Show total DC voltage combined output on the roof on the 3-line diagram or plan sheet #6, and verify compliance with NEC 690.7. 7 Verify and indicate on the plans the required Ventilation and location for the Energy Storage System is in compliance per Manufacturers Recommendations and NEC 706.10(A) thru (E). Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |