Permit Number: T22CM06646
Parcel: 127146010

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM06646
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 Verify what device or equipment will be utilized to initiate the Rapid Shutdown function and apply the ‘Rapid Shutdown’ label to this device or equipment. NEC 690.56

2 Verify the location of the Rapid Shutdown device or equipment complies with NEC 690.12(C).

3 Provide a grounding detail on the plans for the New Electrical Service per NEC 250 and the module racking system. Also verify NEC 690, Part 5.

4 Provide evidence on the electrical plans that the Rapid Shutdown function meets the requirements of NEC art 690.12(B)(1)(2)(3)(4), boundaries around modules and maximum voltage requirements.

5 Verify Ground Fault and Arc Fault protection is provided NEC 690.41(B), 690.11.

6 Show total DC voltage combined output on the roof on the 3-line diagram or plan sheet #6, and verify compliance with NEC 690.7.

7 Verify and indicate on the plans the required Ventilation and location for the Energy Storage System is in compliance per Manufacturers Recommendations and NEC 706.10(A) thru (E).

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.