Permit Number: T22CM06586
Parcel: 141071410

Address:
7215 S KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM06586
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/12/2022 STEVE SHIELDS ZONING REVIEW Approved
09/12/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/13/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018.
09/13/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a seal on the cover sheet of the plan set. A permanently legible imprint of the registrant's seal and signature shall appear on the cover, title, index page, or first sheet of each set of project specifications. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2018, for business/storage occupancy (a bottled water dispenser is not recognized as a substitute for a drinking fountain). Reference: Sections 1109.5 and 2902.1, IBC 2018.
09/13/2022 ROBERT SHERRY WATER REVIEW Completed
09/14/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed
09/16/2022 JVINCEN1 FIRE REVIEW Approved
09/21/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved