Permit Number: T22CM06227
Parcel: 113023000

Address:
1069 E IRWIN PL

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM06227
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
08/16/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM06227
1069 E Irwin Pl – R-2 RCP
New SFR (1st Review)

TRANSMITTAL DATE: August 16, 2022

Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the R-2 RCP zone (UDC 4.7.9). A single-family residence is a permitted use in this zone (Table 4.8-2).


1. Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. As wall heights were not provided from design grade Zoning has added 6” to the provided dimension of 23’-6” for a total of 24’-0”. Based on the platted, S04-113, perimeter yard setbacks of 10’-0” or ¾ the height of the exterior wall, the required perimeter yard setback from the proposed SFR to the north property line is 18’-0”, proposed setback is 10’-8”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback,
DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

The following comments need to be addressed prior to applying for the DDO as addition comments maybe forth coming:

1. Per UDC Article 6.4.5.C.2.b.(2).(c), “The distance between the street pavement edge and the parking structure is eight feet or less” but the plot plan shows 8.5’

2. Street perimeter yard setbacks for the main structure are based on UDC Table 6.4.5.C-1, ADT of 140 or less, the greater setback resulting from the alternate measurement is required. As no setback dimensions from the main structure to the street property line Zoning cannot verify if the structure meets setbacks.


If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/16/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/17/2022 AWARNER1 NPPO REVIEW Approved