Permit Number: T22CM05873
Parcel: 123072210

Address:
2316 E HELEN ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM05873
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review Section

PROJECT:
T22CM05873
2316 E Hellen St – R-1
Bedroom Addition (1st Review)

TRANSMITTAL: August 8, 2022

Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A.

1. Provide wall height dimensions on the west elevation from design grade to where the wall meets the eave at the peak. Based on the 6’-0” perimeter yard setback shown on the plot plan and the 9’-0” height shown on the elevations the proposed wall exceeds the height allowed for a 6’-0” setbacks. A Design Development Option (DDO) maybe required once the requested height dimension is provided.

2. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf.
a. The plot plan shall be drawn at an Engineering scale, i.e. 1” = 10’, 1” = 20’.
b. Provide a lot coverage calculation on the plan.
c. Show the utility lines on the plans.
d. Provide the legal description, “OLSENS AMENDED N135' LOT 6 BLK 38
e. on the plan.
f. Provide the zoning of the parcel and all adjacent parcels.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/08/2022 SCABRAL1 ENGINEERING REVIEW Passed
08/15/2022 AWARNER1 NPPO REVIEW Approved
08/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05873

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Indicate on Title sheet square footage of addition and square footage of existing house.
2. Plans make reference to California building and energy code. Reference correct Codes.
3. Clarify what exactly is being demolished.
4. Indicate on plans section view of foundation, include grade levels and steel schedule
5. Indicate on plans framing details for new work.
6. Indicate on plans dowel details into existing slab.
7. Indicate on plan vapor barrier for new slab.
8. Indicate on plans how project complies with Energy Code, indicate insulation details, air barrier details, window shading details, etc.
10. Cloud all changes


MECHANICAL REVIEW COMMENTS:
Denied
1. Provide listing details for exterior tankless water heater.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
Indicate on plumbing plan size of drainage pipe and venting location for fixtures.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov