Permit Number: T22CM05854
Parcel: 127121200

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM05854
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2022 SCABRAL1 ENGINEERING REVIEW Passed
08/15/2022 STEVE SHIELDS ZONING REVIEW Approved
08/15/2022 JVINCEN1 FIRE REVIEW Approved
08/15/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/19/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM05854

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

1. A500 1202.6 Please coordinate with the Mechanical Engineer to provide proper clearances for the type I hood to combustible materials and or provide protection details per the mechanical code 507.2.6




If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/24/2022 ROBERT SHERRY WATER REVIEW Reqs Change Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
08/24/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. With respect to detail 2/P1.2, all of the vents (except for vents serving interceptors located outdoors) shall rise vertically (i.e. an angle greater than 45 degrees) to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2018.
2. Correct Plan Note 8 on sheet P5.0. The gas is to supply MUA-1, not RTU-2, which is a heat pump. Reference: Section 107.2.1, IBC 2018.
08/25/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations and details to show that the Type I hoods are supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018.
2. Show that combustible materials (e.g. plywood) are not located within 18" of the Type I hoods. Reference: Section 507.2.6, IMC 2018.
08/29/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 The option to use ASHRE 90.1 for energy lighting and power requires automatic control for receptacle at 50%. Please provide this information on the power and lighting plans. Show how this requirement is addressed in detail.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.