08/11/2022 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T22CM05805
925 E Mill St
TI: Millville Studios (1st Review)

TRANSMITTAL DATE: August 11, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. As it appears you are proposing a change of use from Commercial Storage to Technical Service with an accessory General Merchandise Sales use, one of the following is required:
a. Provide an approved Certificate of Occupancy for a use with a motor vehicle parking requirement of one space per 300 sq. ft. gross floor area;
b. Demonstrate that the required vehicle parking for these uses is provided on site; or
c. Show that you meet the requirements of UDC 3.3.3.H in addition to complying with UDC 3.3.3.H.9.a or .b, specifically.

If any of the above cannot be met, a development package is required. The DP is a separate submittal and shall be submitted at https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type "Site Review."

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov.
08/11/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/16/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/19/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed
08/22/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/22/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise detail 206 (lift station) to provide a full-open valve on the discharge side of the integral check valve. Reference: Section 712.2, IPC 2018.
2. Verify that the connection point for the 1-1/2" forced waste pipe to the building drainage system is at least 10 pipe diameters from the base of any soil or waste stack or any fixture drain. Reference: Section 712.3.5, IPC 2018.
08/22/2022 ROBERT SHERRY WATER REVIEW Reqs Change Show the location of the reduced pressure backflow assembly on the drawings; indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
08/24/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/15/2022 JVINCEN1 FIRE REVIEW Reqs Change Confused about fire sprinklers. Existing documents show the basement was sprinklered.
-Does the basement have fire sprinkers?
-Fire sprinklers required in basement per IFC 903.2.11.1. Install fire sprinklers in basement or show how you meet 903.2.11.1 & 903.2.11.1.3.