08/01/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05678

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide Structural Calculations for New 3.5x9 GLB Roof Joists supporting New Mechanical Units. The Calculations submitted only considered roof Dead and Live Loads. Verify if the Joists size is adequate where the RTU’s are present.
2. Provide Structural Calculations for New 8.75x16.5 GLB Roof Girder supporting New Mechanical Units. The Calculations submitted only considered roof Dead and Live Loads. Verify if the Girder size is adequate where the RTU’s are present.
3. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.


BUILDING REVIEW COMMENTS:
Denied
1. Cover Sheet: The allowable area provided is not correct in reference to the use and construction type. Provide correct allowable areas. Additionally, provide clarification on the construction type. Ensure the provided constructed type is correct.
2. Sheet A02: The building code data table is incomplete and incorrect. Provide all necessary information.
3. Sheet A02:Provide a total updated calculated occupant load that includes the areas that are not in scope.
4. Sheet A02:The occupant load for the fixed seating is incorrect. Provide a corrected occupant load along with the calculations in accordance with Section 1004.6.
5. Sheet A02:The occupant load for the juice bar is incorrect. This occupant load factor does not appear on Table 1004.5. The juice bar would be part of the open area. Provide a corrected occupant load.
6. Sheet A02:The exit plan does not indicate the width of exit access components or travel distances. Provide all necessary dimensions and travel distances.
7. Sheet A02: The construction type listed is not a construction type that is recognized by the IBC. Provide a corrected construction type in accordance with Chapter 6.
8. Sheet A02: Show all exit lighting on the exit plan in accordance with Section 1013.
9. Show all existing floor plans.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. Sheet E4.0: Panel VIP CB 29, 31 for CU-3 should have a 30-amp CB or smaller to match HVAC Equipment schedule on sheet E2.0. Otherwise upsize fused disconnect and wire on sheet E2.0.
2. Sheet E4.0:General Note #3 is unreadable.


PLUMBING REVIEW COMMENTS:
Denied
1. Add Plumbing plans with illustrations, information, specifications, & fixture schedule for the relocated & added restroom fixtures shown on plan pages D1.0 & A1.0. and for all the plumbing related work involved with the added Juice Bars. -IPC A106.3.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/09/2022 PCAMARE1 ENGINEERING REVIEW Reqs Change See Zoning comments
08/09/2022 PAUL CAMARENA ZONING REVIEW Reqs Change REVIEW TRANSMITTAL

FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM05678
TI (1st Review)
2130 N ORACLE RD Zoning C-2

TRANSMITTAL: August 9, 2022

1. As there are proposed changes to the site a Development Package
shall be submitted and approved prior to approval of this building permit.



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
08/09/2022 PCAMARE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/25/2022 ROBERT SHERRY WATER REVIEW Completed
09/08/2022 JVINCEN1 FIRE REVIEW Reqs Change Resolve building comments.