| 08/15/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Ref; Plan Sheet A1-10T, E1.OT, E3.62T. 1. Provide a detailed description on the plans that describes in detail the scope of work associated with the Deltas 3 and 4 Revisions. 2. The Exterior Lighting Fixture Schedule on plan sheet E3.62T and E1.OT shows both ‘ZX1L’ and ‘ZX2’ pole mounted luminaires clouded with Delta 3 and 4. Is this the case? Please clarify. 3 Provide an up-to-date Outdoor Lighting Calculation table on the plans. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC) |