Permit Number: T22CM05285
Parcel: 132150210

Address:
801 E 47TH ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05285
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05285

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Provide an existing floor plan showing the current.
2. Provide a thorough egress plan.
3. Provide a detailed narrative of the extraction process for this facility. The narrative needs to be extremely detailed of the entire process to ensure proper code compliance.
4. Provide the quantities of all chemical used in the extraction process and the proposed storage arrangements for these chemicals.



MECHANICAL REVIEW COMMENTS:
Denied
1. Provide the documentation from the odor mitigation plan T185SA00450.
2. The data provided in the outdoor air calculation tables do not match the required data from Table 403.3.1.1. Additionally provide the source of the data that is referenced in these calculations.
3. The plans show no indication of proper mechanical exhaust for the processing space. Provide a narrative on how the space is to be exhausted.
4. Show the location of all growing equipment along with all the manufacturer specifications.
5. Please provide a COMcheck that indicates compliance for new mechanical system and scan that data onto one of the mechanical sheets. This provides evidence the mechanical system is in compliance.


ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/29/2022 SSHIELD1 ENGINEERING REVIEW Passed
07/29/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/03/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM05285
801 E 47th St – I-1
Marijuana Dispensary Off-Site Cultivation Location (1st Review)

TRANSMITTAL: August 3, 2022
This site is located in I-1 Zone (UDC 4.7.29). Marijuana Dispensary Off-Site Cultivation Location is an allowed use in the zone (UDC Table 4.8-5), subject to Use Specific Standards 4.9.9.E.2 and 4.9.13.Q.

1. The Marijuana Use Authorization Letter (T21SA00161 has expired and a new one is required. As stated on the authorization letter provide a copy of the new letter with the submittal of your improvement plans. Contact for requirements is Loran Shamis at Loran.Shamis@tucsonaz.gov.

2. Cleary demonstrate how the requirements of UDC Article 4.9.9.E.2.k are met.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/09/2022 ROBERT SHERRY WATER REVIEW Completed
08/18/2022 JVINCEN1 FIRE REVIEW Reqs Change -Provide hazardous materials mangement plan per IFC 5001.5.1. Also see appendix H for guidance.
-Provide hazardous materials inventory statement per IFC 5001.5.2. Also see appendix H for guidcance.
-Indicate if CO2 enrichment is used. If used, shall comply with IFC 5307.4. Gas detection system shall be required with all requirements of 5307.4.3. Approved/permitted mechanical shall meet IFC 5307.4.4

Final Status

Task End Date Reviewer's Name Type of Review Description
08/18/2022 VVERA1 OUT TO CUSTOMER Completed