Permit Number: T22CM05063
Parcel: 140410010

Address:
3350 E MEDINA RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05063
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2022 WBERGER1 ENGINEERING REVIEW Passed
07/13/2022 WBERGER1 ZONING REVIEW Approved
07/13/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/15/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05063

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
N/A

BUILDING REVIEW COMMENTS:
Denied
1. Sheet CVR1.0: The occupancy group is listed as F-1. However, under the occupancy separation it is also listed as F2. Correct the miscorrelation.
2. General: It appears that combustible storage will be a part of this permit. Ensure all combustible storage meets all the requirements of Section 413.1 and the IFC. Provide clarification on the storage strategies in this project.
3. General: Combustible dust will be a part of the manufacturing process. Ensure compliance with Section 426.1, NFPA 664 and the IFC. It appears that these codes and standards have not been reviewed due to the lack of mechanical drawings and exhaust systems.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
No mechanical plans submitted. no mechanical work is indicated in their scope of work
approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved



PLUMBING REVIEW COMMENTS:
Denied
First Plumbing review:
1). Plan page A1.0 shows water tanks & chillers. do these items or any other equipment require make up water connections? If yes add plumbing illustrations & information to plan set. -IPC 106.3.5
2). Does any equipment on plan page A1.0 require gas connections? if yes add gas illustrations & information to plan set. - IFGC 106.3.5


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/04/2022 ROBERT SHERRY WATER REVIEW Completed
09/06/2022 JVINCEN1 FIRE REVIEW Reqs Change Resolve building comments

john.vincent@tucsonaz.gov
5203495581

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2022 VVERA1 OUT TO CUSTOMER Completed