Permit Number: T22CM05039
Parcel: 12112044D

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05039
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05039

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
Conditions of approval: An engineered fill of minimum 18" thickness needs to be provided below foundations as per the geotech report recommendations as the structural design is based on soil bearing capacity linked to the engineered fill. Foundation notes and details are lacking this detail but it needs to be executed in the field else a revised foundation based on reduced soil capacity of 1500 psf would need to be provided for review and approval.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Denied
1. Sheet E4.0: For NEW SERVICE ENTRANCE SECTION, provide date maximum available fault current calculation was performed for contractor to fabricate label. NEC 2017, 110.24.
2. Sheet E1.0: Provide office furniture layout for Office 102 to verify clearance requirements for VFD equipment. NEC 2017, 110.26.
3. Sheet E1.0: Wash Bay Room electrical equipment tags not fully legible.
4. Sheet E4.0: For transformer TL secondary taps, sheet keynote 9, clarify which tap rule is being used. 240.21(C) contains several tap options. If claiming 10' tap rule, specify the maximum length of secondary transformer TL conductors to both CWA and CWB. NEC 240.21(C)(2).


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Sanitary sewer continuation on plan pages P1.1 & C4.3 don't correlate. -IPC 106.3.1
2). Washer drains can't connect to double sanitary tee. on plan page p3.1 -IPC 706.3
3). Washers on plan page P2.1 & P3.1 need to discharge to an lint interceptor due to multiple washers doesn't meet the exception. -IPC 1003.6
4). Washers on plan pages P2.1 & P3.1 require hot water. -IPC 607.1
5). Add keynote symbols next to each carwash bay hose faucet that correlates to the non-potable verbiage on P2.1 notes - IPC 106.3.1, 608.9.1
6). All hose bibs on plan page P2.1 need shut off valves -IPC 606.2
7). Floor sinks that connect to trench drains on plan page P2.1 & P3.1 need P-traps, -IPC 802.3
8). Trench drain outlet connections on plan pages P2.1 & P3.1 need P-Traps -IPC 1002.1
9). Change Grease interceptor detail on P3.1 internal note to 6" DIA pipe & fittings to correlate with remainder of plan set, not 4" -IPC 706.3
10). Plan Page P2.1 isn't clear if water softener connection is before or after backflow preventer. -IPC 106.3.1
11). Plan Page P3.1 doesn't list water softener info -IPC 303


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/26/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM05039 – DP22-0053
5225 E Speedway Blvd – C-2
Car Wash (1st Review)

TRANSMITTAL: July 26, 2022
This site is located in C-2 Zone (UDC 4.7.21). Auto washing is an allowed use in the zone (UDC Table 4.8-4, subject to Use Specific Standard 4.9.13.E.

1. As DP22-0053 has not completed the first review Zoning is not able to compare the building plans to the DP. Once the 1st review of the DP is completed and comments addressed Zoning will review the building plans for compliance with the DP. Additional comments maybe forth coming. Zoning cannot approve the building plans until the DP is approved by all review agencies.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/26/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/03/2022 ROBERT SHERRY WATER REVIEW Completed
08/18/2022 JVINCEN1 FIRE REVIEW Reqs Change Indicate in code analysis if building will be sprinklered. Backflow notes indicate the building will have fire sprinklers however no notes in deferred submittals.

john.vincent@tucsonaz.gov
5203495581
08/30/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2022 VVERA1 OUT TO CUSTOMER Completed