Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM04824
Parcel: 107131910

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM04824
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Electrical line diagram, panel schedules.

The previous review comments are not completely addressed.

Indicate electrical service riser conduit, conductor quantity, sizes and types.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.