Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM04824
Parcel: 107131910

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM04824
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 Indicate electrical service riser conduit, conductor quantity, sizes and types.

2 Why does the new electrical plan show the service bus rated at 300 amps and the 3 main breakers at 125 amps each (375 amps total)?

3 Indicate wiring methods for reconnection to the existing feeders to each dwelling unit. Indicate feeder sizes, Existing and New. Verify OCPD’s in the new service equipment is not oversized for the existing feeders and sub-panels. NEC 240.12.

4 Why did the first submitted plan show the new service with only 30-amp main breakers and the new plan shows 125-amp main breakers? Provide load calculations to verify what the actual demand is.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.