Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T22CM04580
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM04580 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied Sheet S-001.00 – 2018 “ARIZONA” INTERNATIONAL BUILDING CODE is referenced. Please use applicable building code. City of Tucson IBC Local Amendments • Amendments to the 2018 International Building Code Sheet S-100.00 – Overall building dimension size in Sheet LP-1 do not match with foundation building plan dimensions. Coordinate building size dimensions. Sheet S-100.00 – Provide slab depression dimensions and details cross referencing architectural drawings. BUILDING REVIEW COMMENTS: Denied Sheet GN001.00 – Provide complete applicable codes. City of Tucson IBC Local Amendments • Amendments to the 2018 International Building Code • Amendments to the 2018 International Energy Conservation Code • Amendments to the 2018 International Fuel Gas Code • Amendments to the 2018 International Mechanical Code • Amendments to the 2018 International Plumbing Code • Amendments to the 2017 National Electrical Code • Amendments to the 2018 International Fire Code • City of Tucson/Pima County Outdoor Lighting Code • ICC A117.1 - 2009 Accessible and Usable Buildings and Facilities (by reference) Sheet GN001.00 – Fire Alarm is required however no fire alarm plans submitted. Is fire alarm part of deferred submittals? Clarify scope. Sheet GN001.00 – Provide demolition/existing floor plan to clarify the new scope of work. Sheet G002.00 – Sheet index and submitted sheets do not match. Total count (82 pages) and sheet names do not match (81 pages). For example, Sheet C-01 not in sheet index. Please submit sheets/title that match the sheet index. Sheet A002.00 – Required 36-inch egress width is not provided at Southwest portion of the kitchen. Sheet P200 shows clear width of 1’-9 ¾” and 2’ – 9 3/8” which do not meet required 36 inch. Provide complete clear width in front of appliances. Sheet A005.00 – Provide trash enclosure floor draining direction and slope in 05/A005.00. Sheet A120.00 – Provide locations and details of secondary (emergency overflow) drains or scupper per 2018 IBC section 1502.2. Sheet A310.00 – EIFS special inspections shall be required for all EIFS applications per 2018 IBC 1705.16. Provide statement and schedule for this inspection per Chapter 17. EIFS not in Sheet S-002.00. Sheet A800.00-A804.00 – Specifications text overlaps and illegible. The text goes beyond the sheet boarder. Provide legible texts, Typ. MECHANICAL REVIEW COMMENTS: Denied Sheet G006.00 – Only up to 2 of 10 pages submitted. Please submit complete envelope compliance certificate set (up to 10 pages). ELECTRICAL REVIEW COMMENTS Denied Sheet E140 – Provide light budget calculations and considerations per 2012 City of Tucson/Pima County Outdoor Lighting Code. Provide lumen calculation on plans per section 104.2.1. PLUMBING REVIEW COMMENTS: Denied Sheet P100 – City of Tucson Amendments to the 2018 International Plumbing Code section 1003.3 grease interceptors states hydromechanical grease interceptors may be used when there are four (4) or fewer fixtures while total of 11 fixtures are connected to grease waste line. Grease waste DFU of 45 (45-66) calls for 1500 minimum size (gallons) in gravity grease interceptors table. Provide grease interceptors calculations and explanations per City of Tucson Amendments to the 2018 International Plumbing Code section 1003.3 grease interceptors. If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 07/07/2022 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan (Utility Plan, C-04, only shows a 4" fire service line to the building). Provide the size of the water meter serving this building and the size of the backflow preventer associated with the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018. 2. Clarify the intended size of the water service line. The domestic water calculations on P100 calls for a 1.50" line but the water supply plan on P200 shows a 1.25" water service pipe. Reference: Section 107.2.1, IBC 2018. |
| 07/12/2022 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | See Zoning comments |
| 07/12/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM04580 7980 E Speedway Blvd – C-1 Food Service (1st Review) TRANSMITTAL: July 12, 2022 This site is located in C-1 Zone (UDC 4.7.20), a Food Service use is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standard 4.9.4.M.1 & 5 and 4.9.13.O. 1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 07/12/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 08/08/2022 | JPEELDA1 | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/08/2022 | VVERA1 | OUT TO CUSTOMER | Completed |