Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM04231
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/20/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S1.2 (Existing Foundation Plan); Sheet A21 (Floor Plan): It does not appear some of the new 2x4 stud walls indicated on the Existing Foundation Plan match the new walls indicated on the Floor Plan. Please verify. 2. Sheet A21; Floor Plan: Please indicate all new Wall Types on the new walls indicated on this plan. 3. Sheet A42; Mounting Heights: Please indicate the dimension of the vertical grab bar from the floor. 4. General: Please provide written responses to all review comments. |
06/21/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. |
06/21/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.. |
06/21/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
06/23/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | How are the bathroom exhaust fans controlled? Please show this on the electrical plans. Ref; 2018 IBC 107.2.1, 2017 NEC. |
07/01/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
07/01/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
07/01/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/18/2022 | JPEELDA1 | FIRE | REVIEW | Approved |