Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM04198
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/27/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Ref; Plan Sheet #4. The Panel schedule for the new panel for replaced panel ‘B’ is not legible due to print overlapping. Please revise. Provide a complete luminaire schedule and verify shop lighting complies with NEC art 511.7(B) where applicable. Verify NEC compliance for the Paint Booths per NEC art 516. Are receptacles or any other electrical devices being replaced? If yes, please specify on the power and or lighting plans. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 06/28/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Item #3 in the scope of work calls for two paint booths to be replaced. Provide complete mechanical details of the replacement, including all of the specifications for the two booths. Reference: Section 107.2.1, IBC 2018. |
| 07/14/2022 | JGARCIA1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Include a short narrative of the project and a code analysis (Occupancy Classification, Construction Type, SF). |