Permit Number: T22CM03838
Parcel: 123153460

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM03838
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/09/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/09/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/15/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Provide GFI protected receptacles in the kitchen areas as required per NEC 210.8(6).

2. The electrical line diagram does not correlate with the panel schedule. Line diagram shows 100 amp panel, the panel schedule shows 200 amp. Please clarify.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/16/2022 NGARCIA3 OUT TO CUSTOMER Completed