Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM03647
Parcel: 10504026P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM03647
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM03647

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Provide duct smoke detector for FCU-5 sheet M1 (IMC2018,606.2.1) Complied
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E2.0:
Keynote #8 has misspelling of Handicapped.
Keynote #9 has nonexistent 1/3” C. Provide proper sized requirement.
Keynote #3 may need to be shown at another location too.
Missing Keynotes 6 and 7.
E5.1:
Fuse for FC/3 may be undersized.
Fuse for FC/5 is undersized. Should use Key note #3 vs currently using Key note #6.
E8.0:
Panel A seems undercounted compared to legend count.
Panel B seems undercounted compared to legend count.
Panel D has 3 units shown, not 1 as called out in legend.
Other counts not in agreement with legend.


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/29/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/29/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM03647 – DP22-0224
655 E River Rd
Tenant improvement (3rd Review)

TRANSMITTAL DATE: August 29, 2022

This comment was not addressed. COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Zoning has reviewed the building plans for compliance with DP22-0224 and although it appears that the plans match until the DP is approved by all review agencies zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/06/2022 JVINCEN1 FIRE REVIEW Approved