Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM03647
Parcel: 10504026P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM03647
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03647

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Provide duct smoke detector for FCU-5 sheet M1 (IMC2018,606.2.1) Complied
Approved/Subject to field approval

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E2.0:
Keynote #8 has misspelling of Handicapped.
Keynote #9 has nonexistent 1/3” C. Provide proper sized requirement.
Keynote #3 may need to be shown at another location too.
Missing Keynotes 6 and 7.
E5.1:
Fuse for FC/3 may be undersized.
Fuse for FC/5 is undersized. Should use Key note #3 vs currently using Key note #6.
E8.0:
Panel A seems undercounted compared to legend count.
Panel B seems undercounted compared to legend count.
Panel D has 3 units shown, not 1 as called out in legend.
Other counts not in agreement with legend.


PLUMBING REVIEW COMMENTS:
Denied
Second Plumbing Review:
1). OK
2). Same- note 59 on plan page M1 only instructs for the location of the high louver Response narrative states there will be a high & low -NFPA99 -9.3.6.5.2.3
3 thru 7 OK
8). Same- P4 doesn't notate the trap seal protection type for the floor drain, only shows trap seal protection method for floor sink-IPC 1002.4.1



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/21/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/21/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM03647
655 E River Rd
Tenant improvement (2nd Review)

TRANSMITTAL DATE: July 21, 2022

This comment was not addressed. COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. This comment was not addressed. Per UDC 3.3.3.G.2.c, as you are reconfiguring an area outside the existing building, a Development Package (DP) is required to be submitted and approved prior to approval of this permit. At a minimum the DP shall meet the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites found at https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. The DP is a separate submittal and shall be submitted at https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type "Site Review."

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/15/2022 JPEELDA1 FIRE REVIEW Approved