Permit Number: T22CM03647
Parcel: 10504026P

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM03647
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03647

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied
Provide duct smoke detector for FCU-5 sheet M1 (IMC2018,606.2.1)


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E2.0:
Keynote #8 has misspelling of Handicapped.
Keynote #9 has nonexistent 1/3” C. Provide proper sized requirement.
Keynote #3 may need to be shown at another location too.
Missing Keynotes 6 and 7.
E5.1:
Fuse for FC/3 may be undersized.
Fuse for FC/5 is undersized. Should use Key note #3 vs currently using Key note #6.
E8.0:
Panel A seems undercounted compared to legend count.
Panel B seems undercounted compared to legend count.
Panel D has 3 units shown, not 1 as called out in legend.
Other counts not in agreement with legend.


PLUMBING REVIEW COMMENTS:
Denied
First Review:
1). Sanitary riser on plan page P6 is missing the plumbing/vent illustrations to the P5 fixture as shown on plan page P1. Plan pages need to correlate. -IPC 106.3.1
2). The med gas storage room Louvered vents on plan page M1 need to be located to ensure cross ventilation. -NFPA99 9.3.6.5.2.3
3). Add the med gas storage room louvered vent sizing calculations to plan page M1 or P5 -NFPA99 9.3.6.5.2.1
4). How will the med gas storage room temperature be maintained -NFPA99 9.3.6.7
5). Add med gas room Storage verbiage to door #137 on plan page A6.1 -NFPA99 5.1.3.1.9
6). Add shower base or shower pan materials to plan page P4 - IPC 421.1, 421.5, 421.5.2
7). Add med gas & vacuum piping material types to plan page P4 -NFPA99
8). Add floor drain/floor sink trap primer type & detail to plan page P4. -IPC 1002.4.1
9). Add fixture spacing measurements to plan page A4 - IPC 404.2, 405.3.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/07/2022 WBERGER1 ENGINEERING REVIEW Passed
06/07/2022 ROBERT SHERRY WATER REVIEW Completed
06/07/2022 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T22CM03647
655 E River Rd
Tenant improvement (1st Review)

TRANSMITTAL DATE: June 7, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Per UDC 3.3.3.G.2.c, as you are reconfiguring an area outside the existing building, a Development Package (DP) is required to be submitted and approved prior to approval of this permit. At a minimum the DP shall meet the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites found at https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. The DP is a separate submittal and shall be submitted at https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type "Site Review."

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov.
06/07/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/28/2022 JPEELDA1 FIRE REVIEW Reqs Change Type an quantity of Med gas to be used/stored shall be supplied. Notes shall be added:
Fire alarm plans shall be submitted to TFD
Fire sprinkler plans shall be submitted to TFD
Owner shall obtain an above ground storage tank permit from TFD
Owner shall obtain a flammable combustible gas permit from TFD

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
Tucson Fire Department

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2022 VVERA1 OUT TO CUSTOMER Completed