Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM03587

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approived


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
es2 POOL AMENITY AREA NEW - LIGHTING PLAN:
Note #2 seems to conflict with (E) fixtures indicated.
Panel SB is missing a 2 Pole 30-amp CB per note 1 on sheet es1.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
Second Plumbing Review:
1) COMPLIED-Per plan page S2.0 * x1.3 this an open span wood roof with no decking, how will the P1 sinks on plan page MP1.0 Be protected from receiving storm water? -IPC 1101.3 **** Plan pg.MP4.0 Has added sink cover, Field verify at inspection****
2). COMPLED- BBQ grills beneath over head construction need hoods. see plan page X1.3 update all affected pages. -IFGC 623.5 **** Plan Page S2.0 has removed construction above gas BBQ, Field verify at inspection****
3). OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/02/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/02/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/02/2022 STEVE SHIELDS ZONING REVIEW Approved
08/15/2022 JVINCEN1 FIRE REVIEW Approved