Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM03587
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2022 JPEELDA1 FIRE REVIEW Reqs Change Provide occupant load and exiting plan for the common area.
Show that the gate hardware meets the exiting requirements for the occupant load.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@tucsonaz.gov
520-837-7033Fire Plans Examiner
05/26/2022 ROBERT SHERRY WATER REVIEW Completed
05/27/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03587

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Provide a basic code analysis for the renovation of the reception space. (existing and affected areas, occupancy class, occupant load, etc.)


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
es2 POOL AMENITY AREA NEW - LIGHTING PLAN:
Note #2 seems to conflict with (E) fixtures indicated.
Panel SB is missing a 2 Pole 30-amp CB per note 1 on sheet es1.


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1) Per plan page S2.0 * x1.3 this an open span wood roof with no decking, how will the P1 sinks on plan page MP1.0 Be protected from receiving storm water? -IPC 1101.3
2). BBQ grills beneath over head construction need hoods. see plan page X1.3 update all affected pages. -IFGC 623.5
3). Add Gas grill manufacturer & model number to plan page MP4.0 -IFGC 301.3


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/07/2022 PAUL CAMARENA ZONING REVIEW Reqs Change REVIEW TRANSMITTAL

FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM03587
Building Plans (1st Review)
4555 S MISSION RD Zoning RV

TRANSMITTAL: June 7, 2022

1. Zoning has reviewed the building plans for compliance with the associated unapproved Development Package DP22-0126. Zoning cannot approve the building plans until the DP is approved.


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
06/07/2022 PCAMARE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/21/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments