Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM03231
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | Until grading plan DP22-0079 has been approved Zoning cannot approve the building plan. |
| 05/11/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549. Show a minimum 300 SF clear solar-ready zone on a roof or framing plan, T103.3. Clarify if the electrical service is overhead sheet 2.1 or underground sheet E1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans. |
| 05/27/2022 | AWARNER1 | NPPO | REVIEW | Approved | |
| 05/31/2022 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | See Zoning comments |
| 06/01/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | House requires fire sprinklers. There is only one hydrant that services this area and the house would require two. Add a note to the cover sheet stating that fire sprinklers will be installed and a permit shall be obtained from TFD. Please contact Tucson Water to upsize the water meter. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@tucsonaz.gov 520-837-7033 Fire Plans Examiner |