Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM03058

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Approved/Subject to field approval.


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
Engineer’s seal is shown as expired, should be updated for future submittals
E1.1A: One of the Keynote #7 notes seems to be referencing a large (112KVA?) Transformer (Mislabeled Keynote #8?) and not a PDU as shown by the other Keynote #7. Probably should be Keynote #8 as it is not used.
E5.2: Keynote #3 not used/shown. Could be one of the Keynote #4 notes.
E6.2: Should show Mini Split fan coil loads in Panel L/B-6 EM.


PLUMBING REVIEW COMMENTS:
Approved