Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2022 GPENNIN1 ENGINEERING REVIEW Passed
04/26/2022 GPENNIN1 ZONING REVIEW Approved
04/26/2022 GPENNIN1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/11/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03058

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Refer to Mechanical Drawings M1.RA and M1.RB. The Drawing shows 2 new 6.5-ton A/C units and 2 New 3 ton Condenser units on existing roof. Provide structural calculations verifying the adequacy of the existing roof members to support the new units. All calculations are to be sealed and signed by the PE registered in State of Arizona.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Approved/Subject to field approval.


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
Engineer’s seal is shown as expired, should be updated for future submittals
E1.1A: One of the Keynote #7 notes seems to be referencing a large (112KVA?) Transformer (Mislabeled Keynote #8?) and not a PDU as shown by the other Keynote #7. Probably should be Keynote #8 as it is not used.
E5.2: Keynote #3 not used/shown. Could be one of the Keynote #4 notes.
E6.2: Should show Mini Split fan coil loads in Panel L/B-6 EM.


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Label the DHWR piping on plan pages M3.0 & M3.1A. -IPC 106.3.1
2). Spec book page 110553-7 Showa compressed gases, the piping illustrations of these gases not shown within the plumbing plans? IPC A106.3.1
3). Label vent for office sink on plan page M.3.1A As AAV or show vent termination. 0IPC 901.2.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/17/2022 ROBERT SHERRY WATER REVIEW Completed
05/25/2022 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/25/2022 VVERA1 OUT TO CUSTOMER Completed