Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2022 ROBERT SHERRY WATER REVIEW Completed
07/05/2022 STEVE SHIELDS ZONING REVIEW Approved
07/06/2022 JPEELDA1 FIRE REVIEW Reqs Change Building is 8,000 sq feet type IIB Construction and rquires a fire flow of 2,000 GPM for 2 hours.Building had 1 hydrant located within 400' but the other hydrant is approximately 440 feet away and exceeds the requirements. Building shall have fire sprinklers installed. Or add an aditional hydrant within 400' of the building.
Note: DP shall be approved prior to CM.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
Tucson Fire Department
08/11/2022 SCABRAL1 ENGINEERING REVIEW Approved