Permit Number: T22CM02945
Parcel: 125121110

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM02945
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2022 WBERGER1 ZONING REVIEW Approved
04/25/2022 WBERGER1 ENGINEERING REVIEW Passed
04/25/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/27/2022 JPEELDA1 FIRE REVIEW Reqs Change Plans shall have a cover sheet that includes but not limited to:
The scope of work
Code references
Occupancy type
Occupant load
Type of construction
If the building has a fire sprinkler and or fire alarm system
Plans shall show an egress plan for the new spaces that also indicates the travel distances

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
05/03/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/09/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide calculations to verify that adequate ventilation will be provided for the new use of the space. Reference: Section 403.3.1.1, IMC 2018.
2. Clarify the operation of the restroom exhaust fan. Provide a minimum exhaust flow rate of 50 CFM per water closet or urinal if the exhaust is continuous, 70 CFM if the exhaust is intermittent. Reference: Section 403.3.1.1 and Table 403.3.1.1, IMC 2018.
05/09/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
2. Provide a vent for the water closet. A common vent is limited to serving two traps or trapped fixtures. Reference: Sections 901.2.1 and 911.1, IPC 2018.
05/09/2022 ROBERT SHERRY WATER REVIEW Completed
05/17/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Are the 2x4 lay-in luminaires all existing? If not, provide compliance with the 2018 IECC.

2. Designate a branch circuit and panel for the new tankless hot water heater, and verify the additional load is within the panels capacity.

3. Provide GFI protection for restroom receptacle.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.