Permit Number: T22CM02751
Parcel: 14101925B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02751
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM02751

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Conditionally Approved
12. Where multiple air handling systems share common return ducts with a combined design capacity greater than 2,000 cfm the return air system shall be provided with smoke detectors in a approved manner. sheet 3M201A (IMC2018,606.2.2) Complied
Approved/subject to field approval

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov