Permit Number - T22CM02698
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2022 STEVE SHIELDS ZONING REVIEW Approved
09/26/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM02698


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Studio will be a conditioned space, using a proposed 1.5-ton Mitsubishi mini-split


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
1. All exterior lighting will be installed in accordance with the 2012 City of Tucson/Pima County Outdoor Lighting Code.
2. All new or replaced 15- and 20-amp outlets shall be tamper proof type. 2017 NEC 210.52.
3. All outlets in the garage shall be GFCI protected. Exterior outlets shall be GFCI protected and be provided with a weatherproof enclosure with “in-use” covers. 2017 NEC 406.8.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No plumbing is included as part of this submittal