Permit Number: T22CM02645
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM02645
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2022 SSHIELD1 ENGINEERING REVIEW Passed
04/21/2022 STEVE SHIELDS ZONING REVIEW Approved
04/21/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/25/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02645


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Provide the address for the property on the drawings.
2. The equipment plan sheet AQ2.3.4a appears to cut off the information from Room OR 19. the remainder of the room is shown on the following sheet. Provide a cut and match line for this room or adjust the information so the room can be viewed on one page.
3. Correct the sheet title for sheet AQ2.3.4c, it appears to have been copied over from the previous sheet and not updated.


MECHANICAL REVIEW COMMENTS:
Denied
1. No MEDGAS review completed.
2. Prepare mechanical calculations to show that outside air and other ventilation requirements are met and balanced. Include a ventilation schedule to drawings


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No plumbing work was included as part of this submittal.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/29/2022 JVINCEN1 FIRE REVIEW Approved
05/05/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2022 VVERA1 OUT TO CUSTOMER Completed