Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM02349
Parcel: 13409010A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM02349
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change CONTACT PIMA COUNTY ADDRESSING TO DETERMINE UNIT/BUILDING NUMBER. NEED PRIOR TO ISSUANCE PH# 520-724-9512 ADDRESSING@PIMA.GOV.
04/05/2022 JPEELDA1 FIRE REVIEW Approved
04/05/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G21; Occupancy; Plumbing Fixture Table: The Occupancy Calculation indicates 44 total occupants, while the Plumbing Fixture Table indicates 45. Please coordinate.
2. Sheet G21; Egress Plan: Per the IBC Section 1017.3, the measurement of the exit access travel distance shall be along the natural and unobstructed path of horizontal and vertical egress travel. Please revise the Egress Plan paths A and B.
3. Sheet G21; Plumbing Fixture Table: Please provide the calculations on this sheet for determining the required plumbing fixtures (Men's Water Closets = 22/125 = 0.18; etc.).
4. Sheet A21; Floor Plan: The Floor Plan indicates only one restroom, while the Plumbing Fixture Table (Sheet G21) indicates a men's and a women's restroom is required. Per the IBC Section 2902.2 (Exception 2), separate facilities shall not be required in tenant spaces with a total occupant load of 15 or fewer. The occupant load of 44 requires separate men's and women's facilities (water closets, lavatories). Please revise.
5. Sheet A21; Wall Types: In Wall W01, please indicate the spacing of the 2x4 wall studs.
6. General: The plans indicate a second story on this structure. Does this project affect access or any other issues to that second floor? Please verify and indicate on the plan.
7. General: Please provide written responses to all review comments.
04/15/2022 IMONSHI1 ENGINEERING REVIEW Passed
04/15/2022 IMONSHI1 ZONING REVIEW Approved
04/15/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
04/19/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Natural ventilation calculations for the second floor are shown on M11 but no ventilation calculations are shown for the first floor. Note that the doors on the storage room will make natural ventilation of the storage room and the utility room impossible. Reference: Section 402.3, IMC 2018.
04/19/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the lavatory using a device conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018.
3. Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.
04/19/2022 ROBERT SHERRY WATER REVIEW Completed
04/25/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Provide GFI protected receptacles as required for the drinking fountain and Kitchen. NEC 210.8, 422.5.

2. Provide full compliance with the 2018 IECC for the lighting.

3. Verify that there is a 120 volt receptacle for the maintenance of the HVAC equipment. NEC 210.63.

Ref; 2018 IBC section 107.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements