Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM02072
Parcel: 14101925B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02072
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Plan Sheet E201.

The electrical line diagram showing the generator feeders and utility power both connected to the stepdown transformer primary and is not utilizing a Transfer Switch in the design to prevent the inadvertent interconnection of normal power (utility) and other sources of supply such as the standby or temp generator. This could be a potential electrical hazardous condition. Please clarify. NEC 702.5.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.