Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM02072
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/30/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. The previous electrical plan review comment is not addressed. The resubmitted plans show the same electrical distribution system on the entire site and location of all the construction trailers, and no mention of the construction trailer or generator in question. The electrical review response letter just states, “This is for a 24x60 office trailer”. The description in the application states “24x60 construction trailer w generator” etc. There are numerous construction/office trailers shown on the plans and the electrical distribution system. For clarity, please have the EE of record identify the construction trailer in question and generator with all necessary electrical information required, including all the electrical connections. Show this on the plan set. Be sure the revised plan is sealed and clouded by the registrant. Revise the scope or description of work shown on the Application if necessary to correlate with the proposed work. See 2018 IBC section 107.2.1. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 07/05/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 07/05/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved |