Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM02018 R1
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. Remove “Preliminary Not for Construction” and add the profession seal to sheet A-1.
2. Provide separate square footages of the dwelling and garage on sheet A-1.
3. All SFR and Duplex plans submitted after July 1, 2009, require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 .
a. Show a minimum 300 SF clear solar-ready zone on a roof or framing plan, T103.3. Model plans should show four typical south facing roof surfaces.
b. Label a double breaker space for future Photo Voltaic on the panel schedule opposite end from the main/supply side, T103.9. Show the future breaker location on the panel schedule.

STRUCTURAL PLANS:

1. Show braced wall panel compliance for (narrow) framed walls with a garage door opening, Table R602.10.5. For prescriptive braced wall structures show a portal frame with hold-downs PFH method, Figure R602.10.6.2, or a portal frame at garage door PFG method, Figure R602.10.6.3, or a continuously sheathed portal frame CS-PF method, Figure R602.10.6.4.

SECTIONS - DETAILS:

1. Show the attic vent opening size using 1 to 150 of attic area with all insulation at the ceiling in compliance with R806.2.

PLUMBING PLANS:

1. Plumbing devices require a manufacturer rating for the intended application, G2406.3. A two-way valve is not appropriate for building drainage. Show a gray drain line to the building exterior without a diverter valve and appropriate connections to the sewer system provided at https://www.tucsonaz.gov/pdsd/water-energy-conservation or provide the spec sheet for a compliant diverter for drainage applications.

ELECTRICAL PLANS:

1. Show the location of a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace, in a utility or laundry room, N1101.14. Add notation to plans.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
09/09/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM02018
2341 E 7th St – R-1
New SFR (4th Review)

TRANSMITTAL: September 9, 2022
This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. This comment was not addressed. The north arrow shown on the site plan, foundation plan, floor plan, roof framing plans are not correct. 7th street is to the south of the parcel.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.