Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM01851
Parcel: 11903430A

Address:
3309 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM01851
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM01851


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.
2. Submit documentation regarding implementation of Special Inspections and Testing program during construction.
3. Refer to sheet 3.1 and Sheet 1.1. The dimensions shown does not match dimensions shown on the Floor Plan Drawing. Verify and make revisions as needed.


BUILDING REVIEW COMMENTS:
Denied
1. Provide a thorough egress plan that indicates the clear egress path through or around the new paint booth.
2. Provide a typical wall schedule that provides details on all wall types.
3. Provide the full manufacturer specification for the paint booth.
(Paint Booth to be deferred per Safebuilt Reviewer and approved by Juan Garcia on 4/7/22)


MECHANICAL REVIEW COMMENTS:
Denied
1. The gas fired unit heater is within 20' of the paint booth. Provide proper separation of the spark producing device in accordance with Section 2403.2.2 of the IFC.
2. Provide all manufacturer specifications for the mechanical systems of the paint booth.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1. Plans need to include a roof drain piping riser diagram along with roof drain, conductor sizes & calculations & piping materials that derive from -IPC 1106.2, 1106.3 , 1102.6, 1102.7. (Per Safebuilt Reviewer 4/7/22- Applicant to disregard this comment)

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/29/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM01851 – DP22-0040
3309 S 12th Ave – C-3
Expansion of Auto Body Repair (1st Review)

TRANSMITTAL: March 29, 2022

This site is located in the C-3 zone (UDC 4.7.22). Trade Service and Repair: Major is a permitted use in this zone (Table 4.8-4). See Use-Specific Standard 4.9.4.X.1.

1. Zoning has reviewed the building plan for compliance with DP22-0040 and although the plans appear to match Zoning cannot approve the building plan until the DP is approved.

2. Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. As heights were not provided frim design grade zoning cannot determine required perimeter yard setback requirements but at a minimum a A Design Development Option (DDO) must be submitted and approved to reduce the required setback to the east property line,
DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov. The 18’-0” height shown on DP22-0040 is not accurate and will affect the DDO requirements.

3. The development package sheet provided in the building set either needs to be the stamped approved sheet, marked as for reference only or removed from the building plan set.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/03/2022 JVINCEN1 FIRE REVIEW Reqs Change See building comments.

john.vincent@tucsonaz.gov
5203495581
04/11/2022 ROBERT SHERRY WATER REVIEW Completed
04/15/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change
04/28/2022 IMONSHI1 ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2022 VVERA1 OUT TO CUSTOMER Completed