Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM01394
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/22/2022 | WBERGER1 | ZONING | REVIEW | Reqs Change | A vacant commercial site must be developed with an identified use and meet all applicable development standards. |
| 03/24/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. See Zoning review comments. 2. Please address the electrical plan review comments and provide a written response 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/24/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |