Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Please provide a grounding detail or show grounding method for the transformer ‘T4’.

2. Provide for warning labels at the electrical equipment or provide a note to comply with NEC 300.45.

Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2022 NGARCIA3 OUT TO CUSTOMER Completed