Permit Number: T22CM00906
Parcel: 11108118F

Address:
3514 E FLOWER ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM00906
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM00906
Building Plan Review (1st Review)
3514 E FLOWER ST Zoning R-2

TRANSMITTAL DATE: ?February ?16, ?2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Please remove any notation of kitchen on the electrical plan for the guest house. A Guest house is not consider a second unit per UDC Section 6.6.3.A " An accessory building shall not be a dwelling unit but may be a building that is used as sleeping quarters by the residents of the dwelling unit in accordance with Sections 6.6.1.A and B. The sleeping quarters may include bedrooms , bathrooms, and a sitting room, provided the building complies with Section 6.6.1.C and is not the dominant use of the property" If a second unit is proposed additional comments may be forthcoming.


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
02/16/2022 SBLOOD1 ENGINEERING REVIEW Passed
02/25/2022 AWARNER1 NPPO REVIEW Passed
02/28/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00906

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. 2018 IRC Table R802.4.1.(2). Revise drawings with rafter size and placement on center for spans including 6' overhang.


MECHANICAL REVIEW COMMENTS:
Denied
1. 2018 IRC Section M1305.1.1. Provide a level service space not less than 30 inches x 30 inches at front or service side of appliance with door open.


ELECTRICAL REVIEW COMMENTS
Denied
1. 2018 IRC Section E3607.3. Revise the electrical plans to show a grounding electrode system serves the sub-panel guest house.


PLUMBING REVIEW COMMENTS:
Approved