Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify for which units gas piping will be installed; The application lists unit 1 and 2 but the gas template shows 1 and 3. Reference: Section 107.2.1, IBC 2018.
2. Show the location of the clothes dryer on the gas piping template and show all of the pipe sizes. Reference: Section 107.2.1, IBC 2018.