Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM00861
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM00861 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Conditionally Approved Approved/subject to field approval ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Denied Second Review: 1 -3 Ok 4). SAME-Label the P8 dialysis box on plan page P2.02 rooms 74008, 74009. -IPC A106.3.1 ** Labeled incorrectly** 5-9 OK 10). SAME- Missing 2nd med gas alarm panel on plan pages. P3.01 & P3.02 NFPA 99 5.1.9.2.1 Requires 2 panels 11-13 OK If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |