Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM00861
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM00861
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2022 ROBERT SHERRY WATER REVIEW Completed
02/28/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00861

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Provide existing square footage.
2. Provide existing occupant load and new occupant load.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
First Review:
1). Sanitary venting for new plumbing fixtures P1,P2,P4.P5,P6,P7 are not illustrated or notated on plan pages P2.01 & P2.02 -IPC A106.3.1
2). Nutri room isometric detail #3 on plan page P2.01 has sink mis-labeled, should be P5. -IPC A106.3.1
3). Drains for ice machines on plan pages P2.01 & P2.02 are not illustrated or notated. Also a waste receptor is not listed on plan pg. P5.01. -IPC 802.1.3
4). Label the P8 dialysis box on plan page P2.02 rooms 74008, 74009. -IPC A106.3.1
5). Demo plan keynote symbols 4 & 9 in patient room 74009A don't correlate with demo keynote legend on plan pg. P2.02 - IPC A106.3.1
6). Demo Keynote symbols 7 & 12 in patient room 74008A don't correlate with demo keynote legend on plan pg. P2.02 -IPC A106.3.1
7). Demo plan keynote symbol 8 in patient room 74034A doesn't correlate with demo keynote legend on plan pg. P2.02 -IPC A106.3.1
8). Demo Keynote symbol 6 for room 74019A doesn't correlate with Demo keynote legend on plan pg. P2.02 -IPC A106.3.1
9). Keynote symbol 2 in front of patient rooms 64003 & 64004 should be keynote symbol 3. Update plan page P3.01
10). Missing med gas alarm panel on plan pg. P3.02 across from nurses' station on side near Room 74024. NFPA 99 5.1.9.2.1 (2)
11). illustrate the med gas piping at this time for rooms 64015, 64015,74008,74009 on plan pages P3.01 & P3.02. -IPC A106.3.1
12). Lavs need ASSE 1070 mixing valves update fixture specs on plan page P5.01. -IPC 419.5
13). Plan page P0.02 Med Gas Notes references NFPA 99 2012, The 2018 International Plumbing Code Chapter 15 References to use NFPA99 2018
03/05/2022 JVINCEN1 FIRE REVIEW Approved
03/08/2022 STEVE SHIELDS ZONING REVIEW Approved
03/08/2022 SSHIELD1 ENGINEERING REVIEW Passed
03/08/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2022 NGARCIA3 OUT TO CUSTOMER Completed